Available models
Model | Description | Code |
---|
Safety relay for emergency stop buttons and safety switches monitoring.
Guided-contact safety relays 2 N.A. + 1 N.C.
EDM Feedback input for external contactors monitoring.
The Start/Restart can be: automatic/manual (AD SRE3) or manual monitored (AD SRE3C).
Both models can be used up to safety Category 3, PL d according to EN ISO 13849-1.
Product certified by TUEV Nord Cert GmbH.
Safety relay outputs | 2 N.O. - 6 A 240 VAC / 24 VDC Each N.O. safety output line is interrupted twice by the two relays |
Response time (ms) | <= 50 |
Start/Restart command according to IEC 61496-1 | AD SRE3 - Automatic/Manual AD SRE3C - Manual monitored |
External Device Monitoring | Yes - EDM feedback input for extra external contactors monitoring |
Signalling | LED indicators for status and supply diagnostic: power, channel 1 and channel 2 |
Power supply (VDC) | 24 -15% +10% |
Electrical connection | On terminal block |
Operating temperature (°C) | -25 ... 55 |
Protection rating | IP 40 for housing - IP 20 for terminal block |
Fastening | On DIN rail fastening according to EN 50022-35 standard |
Dimensions h x w x d (mm) | 99 x 22,5 x 11 |
Technical manuals
Catalogues and Brochures
Model | Description | Code |
---|